Installation Instructions for Innotech Genesis Systems
Edition 011100
4-10
The output circuits are then checked for the opposite condition. For circuits using the NC
contacts, the wire going the C terminal is temporarily disconnected and the associated
device is checked to make sure it is de-energised. For circuits using the NO contacts, a
jumper wire is temporarily connected between the NO and C terminals; the associated
device is checked to make sure it is energised.
Figure 4-4. Checking Digital Output Wiring.
4
41 42 43 4445 46
47
NO NO NO
C C
NC NC
V
AC
V
DC
0V
+
-
V
AC
V
DC
240V
+
-
L1
L1
L2
L2
GENESIS II
DIGITAL
CONTROLLER
TERMINALS
EXTERNAL
DEVICE
DIGITAL
OUTPUT
1
DIGITAL
OUTPUT
2
4
41
42
43
44
45
46
47
NO
NO
NO
C C
NC
NC
V
AC
V
DC
240V
+
-
V
AC
V
DC
0V
+
-
L1
L1
L2
L2
JUMPER
WIRE
DISCONNECT
COMMON
WIRE