Installation Instructions for Innotech Genesis Systems
Edition 011100
3-24
Table 3-12. AI REM Analogue Input Signal Connections.
TERMINAL SIGNAL TERMINAL SIGNAL
ACTIVE REFERENCE
A AI1+ B AI1−
C AI2+ D AI2−
E AI3+ F AI3−
G AI4+ H AI4−
I AI5+ J AI5−
K AI6+ L AI6−
SCREEN Common Screens
3-4.2.5. AO REM Analogue Output Module. The AO REM (Figure 3-13)
provides up to five analogue outputs. Analogue output terminals are located at the bottom
of the module; output signal connections are listed in Table 3-13. Analogue output cables
should be run using twisted pair shielded cable. The screens should be connected to the
signal’s negative output terminal (B, D, F, H or J) in each case.
Figure 3-13. AO REM Analogue Output Module.
Table 3-13. AO REM Analogue Output Signal Connections.
TERMINAL SIGNAL TERMINAL SIGNAL
A AO1+ B AO1- & Screen
C AO2+ D AO2- & Screen
E AO3+ F AO3- & Screen
G AO4+ H AO4- & Screen
I AO5+ J AO5- & Screen
GENESIS
ANALOG OUTPUT
Remote Expansion Module
123
ABCDEFGH I J
RS485 COMMS
CONNECTIONS
END OF
CABLE
JUMPER
POWER
ANALOGUE
OUTPUT
CONNECTIONS