Innotech Genesis II Digital Controller (v5) Manual de usuario Pagina 123

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 124
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 122
Page 123
Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010Chapter 5 – Network Installation
Comms Cables for Port 2
V AC
V
DC
24V
1
2
Isolated from
internal circui t
Connected to
internal circui t
EARTH
L
N
E
Measurements Made
With Earth Wire
Connected
Comms Cables for Port 1
V
AC
V
DC
3.5V
1
2
Isolated from
internal circui t
Connected to
internal circui t
EARTH
L
N
E
Measure AC and DC
voltages: Should be
less than 3.5Vac and
between +10Vdc and
-5Vdc.
Measure AC and DC
voltages: Should be
less than 24Vac and
between +33Vdc and
-33Vdc.
Figure 5-21:  Voltage Check, Innotech Repeater
Vista de pagina 122
1 2 ... 118 119 120 121 122 123 124

Comentarios a estos manuales

Sin comentarios