Innotech Genesis II Digital Controller (v5) Manual de usuario Pagina 106

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 124
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 105
Genesis II Installation Instructions
Page 106 © Mass Electronics Pty Ltd 2010Edition 2.0 dated 06/12/2013
5-3.3.1 Adding Modules to the Comms Link
To insert another module into the Comms link, make a looping connection through it as in Example
A of Figure 5-2 below. Alternatively, use a Innotech Repeater IR11 or IR12 to branch o to the new
module as in Example B of Figure 5-2.
Note that the four devices and Port 1 of the Repeater Module are connected in bus topology. Port 2 of
the Repeater Module and the added device form a separate network linked by the electronics within
the Repeater Module. Always maintain bus topology on the network when adding another module to
the network.
5-3.3.2 Linking Networks in Dierent Locations
When linking networks in dierent buildings, or when linking modules supplied from dierent
switchboards, isolation must be provided to eliminate earth loops.
To expand an REM network, use an Innotech Repeater IR11 as described below in section 5-3.3.3.
To expand a Primary Network, use an Innotech Repeater IR12 as described in subsection 5-3.3.4.
Figure 5-2:  Adding Modules to a Network
Vista de pagina 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 123 124

Comentarios a estos manuales

Sin comentarios